Yaoyu SPBⅠ Environmental protection switch body Environmental protection switch body series

Yaoyu SPBⅠ Environmental protection switch body Environmental protection switch body series

SPB II SWITCH BODY OF SPB SOLID SEAL ENVIRONMENTAL PROTECTION CABINET
SPB II SWITCH BODY OF SPB SOLID SEAL ENVIRONMENTAL PROTECTION CABINET

PRODUCT OVERVIEW

According to the requirements of the standardized customized scheme of the environmental protection gas insulated ring network cabinet, the vacuum interrupter is used to open and close the circuit. Switch insulation parts are mostly recyclable and environmentally friendly thermoplastic clinker, with a recovery rate of more than 90% in the product life cycle. The gas insulating medium can use nitrogen or dry air as the insulating medium to meet the environmental requirements.

COMPLIANCE STANDARDS

GB/T11022-2020

       

High voltage switchgear and control equipment standard common technical requirements                             

GB/T1984-2014

High voltage AC circuit breaker

GB/T1985-2014

High voltage AC isolation switch and earthing switch

GB/T3804-20173.6kV ~ 40.5kV High voltage AC load switch
GB/T3906-20203.6kV ~ 40.5kV AC Metal-enclosed switchgear and Controlgear

 

 Technical Parameter
NUMBER  ITEM UNIT LOAD SWITCH UNIT CIRCUIT BREAKER UNIT ISOLATION UNIT
1  Rated voltage kV 12
2 Rated insulation level 1min Power frequency withstand voltage Phase to Phase、Phase to earth     kV 42
Across isolating distance 48
Lighting impulse withstand voltage Phase to Phase、Phase to earth 75
Across isolating distance 85
3 Rated frequency Hz   50  
4 Rated current A 630 630 630
5 Rated short-circuit breaking current (30times) kA / 20 /
6 Rated active load breaking current(100 times) A 630 / /
7 Rated short-time withstand current(4s) kA 20 20 20
8 Load switch short-circuit making current(3 times) kA 50 50 /
9 Earthing switch short-circuit making current(5 times) kA 50 50 /
10 Rated peak withstand current kA 50 50 50
11 Rated operating sequence / / O—0.3s—CO—180s—CO /
12 Main loop resistance μΩ ≤65 ≤65 ≤65
13 Partial discharge(1.2Ur) pC ≤5 ≤5 ≤5
14

 

Mechanical Life time
   Load switch/Circuit breaker     Times 5000

10000

/
Isolating switch 3000
Earthing switch 3000

MODEL COMPOSITION AND MEANING

Circuit breaker+Isolation switch (below)

a.Type description

b.Installation dimension drawing

Circuit breaker+Isolation switch (upper)

a.Type description

b.Installation dimension drawing

Isolation switch

a.Type description

b.Installation dimension drawing

SCHEMATIC DIAGRAM OF ENVIRONMENTAL PROTECTION SWITCH ADAPTATION MECHANISM

1.SPD07 mechanism schematic

2.SPD10 mechanism schematic

INSTALLATION CONDITIONS

  • Installation ambient temperature:-40℃ to 50℃
  • Installation ambient humidity:The average 24h relative humidity is not more than 95%, the average monthly relative humidity is not more than 92%
  • Installation condition:Installation far away from inflammable, explosion, and strong chemical
  • Installation for no intense shaking
  • Seismic intensity: Level 8
For more product details, click to download PDF to view!

Download

- News

What does solid insulated switchgear consist of?

Solid insulated switchgear is a special type of switchgear that uses solid ...

How is the insulation performance of solid insulated switchgear achieved?

Solid insulated switchgear mainly uses epoxy resin as the main insulating m...

Types of high voltage grounding switch and considerations

The high voltage grounding switch is usually part of the disconnecting swit...

What is the difference between an air circuit breaker (ACB) and a vacuum circuit breaker (VCB)?

An air switch, also known as an air circuit breaker, is a type of circuit b...

GET A QUOTE

Get in Touch

Captcha Code
×