PRODUCT OVERVIEW
According to the requirements of the standardized customized scheme of the environmental protection gas insulated ring network cabinet, the vacuum interrupter is used to open and close the circuit. Switch insulation parts are mostly recyclable and environmentally friendly thermoplastic clinker, with a recovery rate of more than 90% in the product life cycle. The gas insulating medium can use nitrogen or dry air as the insulating medium to meet the environmental requirements.
COMPLIANCE STANDARDS
GB/T11022-2020 |
High voltage switchgear and control equipment standard common technical requirements |
GB/T1984-2014 |
High voltage AC circuit breaker |
GB/T1985-2014 |
High voltage AC isolation switch and earthing switch |
GB/T3804-20173.6kV ~ 40.5kV | High voltage AC load switch |
GB/T3906-20203.6kV ~ 40.5kV | AC Metal-enclosed switchgear and Controlgear |
NUMBER | ITEM | UNIT | LOAD SWITCH UNIT | CIRCUIT BREAKER UNIT | ISOLATION UNIT | |||
1 | Rated voltage | kV | 12 | |||||
2 | Rated insulation level | 1min Power frequency withstand voltage | Phase to Phase、Phase to earth | kV | 42 | |||
Across isolating distance | 48 | |||||||
Lighting impulse withstand voltage | Phase to Phase、Phase to earth | 75 | ||||||
Across isolating distance | 85 | |||||||
3 | Rated frequency | Hz | 50 | |||||
4 | Rated current | A | 630 | 630 | 630 | |||
5 | Rated short-circuit breaking current (30times) | kA | / | 20 | / | |||
6 | Rated active load breaking current(100 times) | A | 630 | / | / | |||
7 | Rated short-time withstand current(4s) | kA | 20 | 20 | 20 | |||
8 | Load switch short-circuit making current(3 times) | kA | 50 | 50 | / | |||
9 | Earthing switch short-circuit making current(5 times) | kA | 50 | 50 | / | |||
10 | Rated peak withstand current | kA | 50 | 50 | 50 | |||
11 | Rated operating sequence | / | / | O—0.3s—CO—180s—CO | / | |||
12 | Main loop resistance | μΩ | ≤65 | ≤65 | ≤65 | |||
13 | Partial discharge(1.2Ur) | pC | ≤5 | ≤5 | ≤5 | |||
14 |
Mechanical Life time |
Load switch/Circuit breaker | Times | 5000 |
10000 |
/ | ||
Isolating switch | 3000 | |||||||
Earthing switch | 3000 |
MODEL COMPOSITION AND MEANING
Circuit breaker+Isolation switch (below)
a.Type description
b.Installation dimension drawing
Circuit breaker+Isolation switch (upper)
a.Type description
b.Installation dimension drawing
Isolation switch
a.Type description
b.Installation dimension drawing
SCHEMATIC DIAGRAM OF ENVIRONMENTAL PROTECTION SWITCH ADAPTATION MECHANISM
1.SPD07 mechanism schematic
2.SPD10 mechanism schematic
INSTALLATION CONDITIONS
In the operation and maintenance of electrical systems, fuse tripping is an...
Solid insulated switchgear is a special type of switchgear that uses solid ...
Solid insulated switchgear mainly uses epoxy resin as the main insulating m...
The high voltage grounding switch is usually part of the disconnecting swit...
GET A QUOTE